Base Load Share
The share of energy consumed while nothing is produced, for example at night and on weekends.
Formula
Base load share = Energy used in non-production time / Total energy used
Base load = Average power in non-production time
Worked examples
- 01Weekend: 280 kW for 56 hours = 15,680 kWh. Week total 98,000 kWh. Weekend share = 16.0%.
- 02Night between shifts: 6 hours at 310 kW on 5 nights = 9,300 kWh.
- 03Shutdown routine cuts weekend load to 140 kW: saving 140 × 56 × 50 weeks = 392,000 kWh per year, at EUR 0.20 per kWh EUR 78,400.
Pitfalls
- Compressed air and ventilation running all weekend are classic base load.
- Some base load is necessary; decide item by item.